CYY-F

HRN HD 603 S1 - DIN VDE 0276-603 - IEC 60502-1
2XY.jpg)
 cable conforms to Low voltage directive
cable conforms to Low voltage directive  max. permitted conductor temperature
max. permitted conductor temperature  min. installation temperature
min. installation temperature  flame retardant acc. IEC 60332-1
flame retardant acc. IEC 60332-1  UV resistant cable
UV resistant cable  cable for direct burial
cable for direct burial CONSTRUCTION
CONSTRUCTION
a) Class 1: solid, round (RE)
b) Class 2: multi wire stranded, round (RM)
Insulation XLPE-compound DIX 3 acc. to HD 603 S1
Filler in multi wire cables) extruded elastomer or plastomer compound
 APPLICATION
APPLICATIONDistribution and signal power cable for static application in ground, within facilities, in cable canals, in concrete, where heavier mechanical stresses are not expected, and the cable has to be protected against mechanical damages, also in conditions where cables are not exposed to heavier tensile strains. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and in other electric plants where heavier current and thermal loads are expected (operating temperature of conductor up to 90 °C).
 
 TECHNICAL DATA
TECHNICAL DATA
Equivalents::
 XP00 acc. to HRN N.C5 230
Cu/XLPE/PVC acc. to BS 5467
Standards: 
HRN HD 603 S1 
DIN VDE 0276-603
IEC 60502-1
Nominal voltage: U0/U = 0,6/1 kV
Test voltage: 4 kV
Temperature range:
Minimum temperature during installation: -5° C
Fixed installed: -20° C to +90° C
At short circuit of max. 5s: 250° C
 
Behaviour in fire:
Flame retardant (self-extinguishing) cable
 acc. to EN 60332-1-2
Minimal inner bending radius: 12xØ multi core,
15xØ single core
| CONSTRUCTION DATA | ||||||||
| Construction | Shape | Outer | Conductor | Current | Current | Cu weight | Cable | Packing* | 
| mm2 | ca. mm | Ω/km | nom.A | nom.A | kg/km | ca. kg/km | ||
| 1 X 10 | RE/RM | 9,3 | 1,83 | 77 | 89 | 96 | 142 | SP40 500 | 
| 1 X 16 | RE/RM | 10,4 | 1,15 | 102 | 115 | 153,6 | 205 | SP45 500 | 
| 1 X 25 | RE | 12,1 | 0,727 | 138 | 148 | 240 | 303 | SP50 500 | 
| 1 X 35 | RE | 13,2 | 0,524 | 170 | 177 | 336 | 394 | SP60 500 | 
| 1 X 50 | RE | 14,8 | 0,387 | 207 | 209 | 480 | 516 | SP60 500 | 
| 2 X 1,5 | RE | 9,5 | 12,1 | 26 | 37 | 28,8 | 126 | SP45 500 | 
| 2 X 2,5 | RE | 10,2 | 7,41 | 36 | 49 | 48 | 157 | SP45 500 | 
| 2 X 4 | RE | 11,4 | 4,61 | 49 | 64 | 76,8 | 200 | SP50 500 | 
| 2 X 6 | RE | 12,4 | 3,08 | 63 | 79 | 115,2 | 253 | SP60 500 | 
| 3 X 1,5 | RE | 9,9 | 12,1 | 24 | 31 | 43,2 | 147 | KOT 100, SP45 500 | 
| 3 X 2,5 | RE | 10,8 | 7,41 | 32 | 40 | 72 | 187 | KOT 100, SP50 500 | 
| 3 X 4 | RE | 12,0 | 4,61 | 42 | 52 | 115,2 | 243 | KOT 100, SP60 500 | 
| 3 X 6 | RE | 13,1 | 3,08 | 53 | 64 | 172,8 | 315 | SP60 500 | 
| 3 X 10 | RE/RM | 16,3 | 1,83 | 74 | 86 | 288 | 495 | DB09 500 | 
| 3 X 16 | RE/RM | 18,5 | 1,15 | 98 | 112 | 460,8 | 712 | DB08 500 | 
| 3 X 25 | RE | 22,7 | 0,727 | 133 | 145 | 720 | 1038 | DB09 500 | 
| 4 X 1,5 | RE | 11,2 | 12,1 | 24 | 31 | 57,6 | 173 | KOT 100, SP50 500 | 
| 4 X 2,5 | RE | 12,2 | 7,41 | 32 | 40 | 96 | 224 | KOT 100, SP50 500 | 
| 4 X 4 | RE | 13,8 | 4,61 | 42 | 52 | 153,6 | 292 | KOT 100, SP60 500 | 
| 4 X 6 | RE | 15,0 | 3,08 | 53 | 64 | 230,4 | 382 | DB08 500 | 
| 4 X 10 | RE/RM | 18,3 | 1,83 | 74 | 86 | 384 | 612 | DB08 500 | 
| 4 X 16 | RE/RM | 21,0 | 1,15 | 98 | 112 | 614,4 | 889 | DB09 500 | 
| 4 X 25 | RE | 27,3 | 0,727 | 133 | 145 | 960 | 1328 | DB10 500 | 
| 5 X 1,5 | RE | 13,3 | 12,1 | 24 | 31 | 72 | 205 | KOT 100, SP50 500 | 
| 5 X 2,5 | RE | 14,3 | 7,41 | 32 | 40 | 120 | 267 | KOT 100, SP60 500 | 
| 5 X 4 | RE | 16,7 | 4,61 | 42 | 52 | 192 | 358 | DB08 500 | 
| 5 X 6 | RE | 18,1 | 3,08 | 53 | 64 | 288 | 471 | DB08 500 | 
| 5 X 10 | RE/RM | 22,4 | 1,83 | 74 | 86 | 480 | 745 | DB08 500 | 
| 5 X 16 | RE/RM | 25,7 | 1,15 | 98 | 112 | 768 | 1066 | DB09 500 | 
 (bk) black
(bk) black
* Packing: KOT 100 = coil 100m, SP = cable on plywood reel, DB = cable on wooden drum