FG7(O)R
PVC insulated and sheathed power cable
CEI UNEL 35375

cable conforms to Low voltage directive max. permitted conductor temperature min. installation temperature flame retardant acc. IEC 60332-1 cable for direct burial
CONSTRUCTION
Conductor    fine wired copper conductor, class 5, acc. to EN 60228

Insulation  rigid EPM rubber (HEPR, hard ethylene-propylene-rubber), quality G7
Sheath   anti-abrasive PVC compound

 

APPLICATION

Distribution and signal power cable for static application in ground, within facilities, in cable canals, in conditions where the cable is not exposed either to systematic mechanical stress or heavier tensile strain. Used in industrial plants or household installations, where heavier current and thermal loads are expec ted (operating temperature of conductor up to 90 °C), in conditions requiring higher flexibility and better resistance to combustion.
 

 TECHNICAL DATA

Standards: 
CEI UNEL 35375

Nominal voltage: U0/U = 0,6/1 kV
Test voltage: 4000 V

Temperature range:
Minimum temperature during installation: -5°C
Fixed installed: -30° C do +90° C
At short circuit of max. 5s: 250° C

Behaviour in fire:
Flame retardant (self-extinguishing) cable
acc. to EN 60332-1-2

Minimal inner bending radius: 4xØ cable

CONSTRUCTION DATA
Construction

Outer
diameter

Conductor
resistance
at 20 °C

Current
carrying
capacity (air)

Current
carrying
capacity (ground)

Cu
weight

Cable
weight

Packing*
mm2 ca. mm Ω/km nom.A nom.A kg/km ca. kg/km  
1 X 1,5 6,0 13,3 25 30 14 49 KOT 100, SP40 500
1 X 2,5 6,4 7,98 33 38 24 60 KOT 100, SP40 500
1 X 4 6,7 4,95 43 50 38 77 KOT 100, SP40 500
1 X 6 6,9 3,3 55 63 58 108 KOT 100, SP40 500
1 X 10 9,5 1,91 77 84 96 159 KOT 100, SP45 500
1 X 16 10,5 1,21 100 63 153,6 218 KOT 100, SP50 500
1 X 25 12,4 0,78 135 136 240 316 KOT 100, SP60 500
1 X 35 13,8 0,55 170 165 336 431 SP70 500, DB08 500
1 X 50 15,3 0,39 209 192 480 562 DB08 500
1 X 70 17,8 0,27 268 233 672 779 DB09 500
2 X 1,5 10,7 13,3 26 35 28,8 157 KOT 100, SP50 500
2 X 2,5 11,6 7,98 30 46 48 193 KOT 100, SP60 500
2 X 4 13,0 4,95 41 57 76,8 258 KOT 100, SP60 500
2 X 6 15,5 3,3 52 74 115,2 367 SP75 500, DB08 500
2 X 10 18,2 1,91 69 96 192 538 DB09 500
2 X 16 20,4 1,21 115 122 307 715 DB10 500
3 X 1,5 11,2 13,3 23 29 43,2 174 KOT 100, SP50 500
3 X 2,5 12,2 7,98 32 36 72 220 KOT 100, SP60 500
3 X 4 13,6 4,95 43 48 115,2 299 KOT 100, SP60 500
3 X 6 16,2 3,3 55 60 172,8 424 DB09 500
3 X 10 19,3 1,91 75 78 288 637 DB10 500
3 X 16 21,5 1,21 100 105 460,8 863 DB10 500
4 X 1,5 12,0 13,3 24 29 57,6 202 KOT 100, SP60 500
4 X 2,5 13,1 7,98 32 37 96 258 KOT 100, SP60 500
4 X 4 14,6 4,95 42 48 153,6 352 KOT 100, SP70 500
4 X 6 17,7 3,3 54 60 230,4 501 DB09 500
4 X 10 21,0 1,91 75 79 384 760 DB10 500
4 X 16 23,5 1,21 100 105 614,4 1039 DB10 500
5 X 1,5 12,9 13,3 24 29 72 232 KOT 100, SP60 500
5 X 2,5 14,0 7,98 32 37 120 301 KOT 100, SP70 500
5 X 4 15,8 4,95 42 48 192 416 DB09 500
5 X 6 19,2 3,3 54 60 288 596 DB10 500
5 X 10 22,6 1,91 75 79 480 896 DB10 500
5 X 16 25,5 1,21 100 105 768 1240 DB12 500
 
 
Sheath colour identification

(gy) grey

* Packing: KOT 100 = coil 100m, SP = cable on plywood reel, DB = cable on wooden drum

 PDF Download